Sign In | Join Free | My futurenowinc.com |
|
Brand Name : RUSEN
Model Number : PCS-A100-MG
Certification : IEC/EN 62109-1/-2, EN 62477-1, IEC/EN 61000-6-2/-6-4, EN 50549-1/-10, NRS 097-2-1:2017 ASGC, GB/T 34120, GB/T 34133, CGC-R46103:2018A, PTPIREE REV1.2: 2024 TYPE B
Place of Origin : China
MOQ : 1pcs
Price : Negotiable
Payment Terms : T/T
Supply Ability : 1000
Delivery Time : 3-30days
Model : PCS-A100-MG
Power Rating : 100KW
Max Efficiency : 97.1%
Operating Temperature Range : -30 ~ 55℃
Battery Compatibility : Li-ion / User-defined
Rated Battery Voltage : 420-850V
Cooling Method : Automatic
Input Voltage Range : 50/60Hz
PV INPUT DC voltage, current : 420-850V
Communication InterfaceInterface : RS485/Wifi/GPRS/CAN/TCP/IP
Certifications : IEC/EN 62109-1/-2, EN 62477-1, IEC/EN 61000-6-2/-6-4, EN 50549-1/-10, NRS 097-2-1:2017 ASGC, GB/T 34120, GB/T 34133, CGC-R46103:2018A, PTPIREE REV1.2: 2024 TYPE B
Warranty : 5 years
• Redundant mode isolation PCS accurately achieves AC/DC power conversion, ensuring efficient transmission and conversion of electrical energy in different power scenarios, and meeting diverse electricity needs.
• Equipped with redundant mode, it automatically switches in case of faults, maintaining stable system operation and greatly reducing the risk of downtime caused by faults.
• With excellent isolation performance, it effectively resists electromagnetic interference and is suitable for fields such as industrial production, data centers, and new energy generation that require strict power supply stability.
Model | PCS-A100-MG |
DC(battery) | |
Voltage range (V) | 420~850 |
Max. current (A) | 270 |
AC(on-grid) | |
Max. output power (kW) | 110 |
Rated output power (kW) | 100 |
Rated voltage (V) | 400 |
Voltage range (V) | 320~460 |
Rated current (A) | 144 |
Max. output current (A) | 159 |
Rated frequency (Hz) | 50/60 |
Frequency range (Hz) | 45~55 / 55~65 |
THDi | <3% |
Power factor | 1leading~1lagging(settable) |
Grid type | 3W+N+PE |
AC(off-grid) | |
Rated voltage (V) | 400 |
THDu | <1% Linear <5% nonlinear |
Rated frequency (Hz) | 50/60 |
Overload capacity | 110% long-term |
General data | |
Max. efficiency | 97.1% |
Ingress protection | IP21 |
Noise emission (dB) | <70 |
Operating temperature (℃) | -30 ~ +55 |
Cooling | Forced air |
Relative humidity | 0 ~95% non-condensing |
Max. operating altitude (m) | 5,000(>3,000 derating) |
Dimension W*D*H (mm) | 800*800*1,900 |
Weight(kg) | 936 |
Self-consumption | <0.5% |
On/ off grid switching | Automatic |
Display and communication | |
Display | LCD touch-screen |
BMS communication | RS485, CAN |
EMS communication | RS485, TCP/IP |
Certificates | IEC/EN 62109-1/-2, EN 62477-1, IEC/EN 61000-6-2/-6-4, EN 50549-1/-10, NRS 097-2-1:2017 ASGC, GB/T 34120, GB/T 34133, CGC-R46103:2018A, PTPIREE REV1.2: 2024 TYPE B |
![]() |
100KW Redundant Mode Isolated PCS Power Converter System Images |